IMPORTANT:
Please follow the installation details below carefully. Guarantee is valid for products installed as described only. 1. The miniBar must be level both directions. 2. There should be 20mm clearance to the wall. 3. Ventilation must be provided as shown in alternatives A, B, C or D. 4. The ventilation duct must at least measure 105mm x the width of the refrigerator. 5. Only the entire cooling unit must project into the duct as shown. 6 Air passing through the duct must not be preheated by any source of heat. 7. Ventilation grills, if used, must have openings of at least 200cm² each.